Conventional Detection

 

Photoelectric Multisensing Technology
SD Series optical smoke detectors and multisensors

 

 

 

SD Series optical smoke detectors are engineered to meet strict UL fire safety codes and effectively respond to a wide spectrum of fires. The SD series multisensors use Photoelectric Technology in conjunction with a fixed temperature heat sensor to further extend its capabilities as reliable smoke detector. SD series detectors are manufactured and tested according to ISO9001: 2000 procedures.

Approvals

   

The Range

SD-269

  2-wire optical smoke detector

SD-269-LED

  2-wire optical smoke detector with remote LED indicator output

SD-268

  2-wire optical multisensor (smoke+heat)

SD-268-LED

  2-wire optical multisensor (smoke+heat) with remote LED indicator   output

SD-169

  4-wire optical smoke detector

SD-168-4H

  4-wire optical multisensor (smoke+heat)

 

                                           

Features and Benefits

  • Photoelectric smoke sensing technology
  • Multisensor is used for a wide range of applications and is highly immune to false alarms
  • Durable sensor head; excellent smoke access
  • N/C (normal/close)-N/O (normal/open) selectable relay output
  • Easy installation and maintenance
  • Attractive sleek housing (white color)
  • Five-year limited warranty

Available Options

  • Remote LED
  • UL Multiple Listing service available

Specification

Model

2/4 Wire

Thermal

Volt. DC

Startup Current (Max)

Alarm Current (Max)

Surge Current (Max)

Startup Time (Max)

Permis. Current (Max)

Freq.

Alarm Contact

Base Model

SD-169

4

-

12/24V

370µA

35mA

-

120 sec

80 mA

3~5 sec

From A/B

P/N854001

SD-168

4

135 F (57°C)

12/24V

370µA

35mA

-

120 sec

80 mA

3~5 sec

From A/B

P/N854001

SD-269

2

-

12~28V

70µA

70mA

160µA

120 sec

80 mA

3~5 sec

-

P/N852001

SD-269-LED

2

-

12~28V

70µA

70mA

160µA

120 sec

80 mA

3~5 sec

-

P/N852001

SD-268

2

135 F (57°C)

12/~28V

70µA

70mA

160µA

120 sec

80 mA

3~5 sec

-

P/N852001

SD-268-LED

2

135 F (57°C)

12/~28V

70µA

70mA

160µA

120 sec

80 mA

3~5 sec

-

P/N852001

 

Smoke Sensitivity

  2.66+/- 1.11% FT Obscuration (UL standard)

Detection Range

  50 foot rating for heat sensor

Start-Up Current

  70 µA Maximum

Alarm Impedance

  For 2-wire models: 100Ω+3V max; 560Ω+3V max (red LED open circuit)

Reset Voltage

  Less than 1 volt

Reset Time

  Less than 1 sec

Alarm Indicator

  Continuously emitting red light

Temperature range

  -10°C to 50°C

Remote Output

  15 mA max, diode gate

Humidity

  0 to 95% RH, noncondensing

Alarm Contact

  For 4-wire: N/O or N/C Operation

 

  Form A: 1.0A@30VDC/0.5A@125VAC

Dimensions

  10mm (dia) x 46mm (ht) with base

Weight

  130g/set with base

 
     

                                               

   
     

  

  

  

  

  

  

  

  

 

BACK